Home>Cable Accessories>Cable Joints>Low Voltage Cable Joints



Prysmian BICON EFRZHMPJ Enhanced Fire Resistance & Zero Halogen Cable Joints and Kits are straight joints for Enhanced Low Voltage Fire Performance (FP) cables with copper conductors: Multi Core 4mm2 to 400mm2.
Part Numbers: EFRZHMPJ3, EFRZHMPJ4, EFRZHMPJ5, EFRZHMPJ6, EFRZHMPJ7, EFRZHMPJ8.
Features and Benefits
Rated voltage 1000V
Tested and approved to :
=> BS EN 50393:2015 – Test methods and requirements for accessories for use on distribution cables of rated voltage 0,6/1,0 (1,2) kV
=> BS EN 61034-2, IEC 61034-2 – Smoke Emission
=> BS EN 60754-1 , IEC 60754-1 – Acid Gas Emission
=> BS 6387:2013 – Test method for resistance to fire of cables required to maintain circuit integrity under fire conditions (categories C,W & Z)
=> BS 8491:2008 – Method for assessment of fire integrity of large diameter power cables for use as components for smoke and heat control systems and certain other active fire safety systems (120Mins)
Use with BS 7846 (F2,F30,F60, F120) Fire Resistant FP Cables
System Requirements : BS 8519 Cat 3 & BS 5266-1 (120min)
Low Hazard Isocyanate Free JEM resin
Twin pack mixing in clear laminate sachets
Extremely low viscosity resin with enhanced adhesion
Rigid glass reinforced phenolic joint shells which are both fire retardant and LSOH.
Slim-line design for use with compression connectors.
Technical Information
LV Straight Joints for 600/1000 Volt fire Performance polymeric insulated SWA cables with copper conductors.
Tested and approved to BS EN 50393 : 2015
Fire tests on completed joints to:
BS 6387 categories C,W & Z
BS 8491:2008 – 120MinsCombined Fire, Impact & Water Jet
Reaction to Fire tests to:
BS EN 61034-2 , IEC 61034-2 – Smoke Emission
BS EN 60754-1 , IEC 60754-1 – Acid Gas Emission
JEM Resin
=> Easier mixing in “Twin Pack” totally enclosed mixing in a clear laminate sachet.
=> Extremely low mix viscosity allows void Free joint filling.
=> JEM Resin is insensitive to moisture and will cure under water.
=> High flash point, non-flammable liquid – No special storage or transport requirements.
=> Does not cause skin sensitisation.
Download the PDF files for more information on Prysmian BICON EFRZHMPJ Enhanced Fire Resistance & Zero Halogen FP Cable Joints.
*Technical Data subject to change without notice.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
| SHELL DIMENSIONS | |
|---|---|
| PART NUMBER | A (mm) |
| PART NUMBEREFRZHMPJ3 | A (mm)405 |
| PART NUMBEREFRZHMPJ4 | A (mm)430 |
| PART NUMBEREFRZHMPJ5 | A (mm)560 |
| PART NUMBEREFRZHMPJ6 | A (mm)740 |
| PART NUMBEREFRZHMPJ7 | A (mm)870 |
| PART NUMBEREFRZHMPJ8 | A (mm)1015 |
| JOINT SELECTION | |
| Conductor | Two Core |
| Conductor4 mm2 | Two CoreEFRZHMPJ-3 |
| Conductor6 mm2 | Two CoreEFRZHMPJ-3 |
| Conductor10 mm2 | Two CoreEFRZHMPJ-4 |
| Conductor16 mm2 | Two CoreEFRZHMPJ-4 |
| Conductor25 mm2 | Two CoreEFRZHMPJ-4 |
| Conductor35 mm2 | Two CoreEFRZHMPJ-4 |
| Conductor50 mm2 | Two CoreEFRZHMPJ-4 |
| Conductor70 mm2 | Two CoreEFRZHMPJ-5 |
| Conductor95 mm2 | Two CoreEFRZHMPJ-5 |
| Conductor120 mm2 | Two CoreEFRZHMPJ-5 |
| Conductor150 mm2 | Two CoreEFRZHMPJ-5 |
| Conductor185 mm2 | Two CoreEFRZHMPJ-5 |
| Conductor240 mm2 | Two CoreEFRZHMPJ-5 |
| Conductor300 mm2 | Two CoreEFRZHMPJ-6 |
| Conductor400 mm2 | Two CoreEFRZHMPJ-6 |