Home>Cable Accessories>Cable Glands & Kits>Industrial Cable Glands & Kits



CCG A2EX-VS Double Compression Cable Gland (0436) is a Hazardous Area Glanding Device for Copper Tape, Braided or Lead-Sheathed Cable. Suitable for indoor, outdoor, Group II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
CCG Part Numbers: 043600-16, 043600, 0436-0, 043601, 043622, 043602, 034633, 043603, 043644, 043604, 043655, 043605, 043666, 043606, 043677, 043607, 043608, 043699, 043609, 043610, 043611, 043612, 043613
Features & Benefits
For indoor, outdoor, Group II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
The inner seal seals on the cable sheath.
A harder outer seal grips the cable, giving it superior cable retention and an IP rating.
Provides 360° earthing to copper tape or lead sheath.
Precision manufactured from high-quality brass (Marine Grade Electroless Nickel Plated™), available in stainless steel 316/316L on request.
Supplied with a thread sealing gasket (parallel threads only).
Type: A2EX-VS
Equipment Protection Levels: Ex db IIC, Ex eb IIC, Ex ta IIIC , Ex nR IIC
Gland Material: Brass (Marine Grade Electroless Nickel Plated™), Stainless Steel 316/316L
Seal Material: Standard Thermoset Elastomer or Extreme Temperature Seals
Sealing Gasket Material: HDPE, Nylon 66 or PTFE
Cable Type: Copper Tape, Braided or Lead Sheathed
Sealing Area: Taper Seal on the Outer Sheath. Compression seal on inner copper sheath
Optional Accessories: Adaptor, Reducer, Earth Tag, Locknut, Serrated Washer and Shroud
Note: The installer should ensure that the materials are suitable for the installation environment.
Installation Standards
IEC/BS EN
IECEx
ATEX
UKEX
INMETRO (Brazil)
TR CU (Russia)
CCC/CNEx (China)
SANS
Ingress Protection
Deluge Protection
Corrosion Protection
Marine ABS
DNV-GL
EMC Compatible
A Hazardous Area is one in which there is potential for an explosion of gases, vapours, mists or dust or a combination of these. Such locations are petrochemical plants, offshore oil rigs, fuel filling stations, timber mills, coal mines, flour mills, paint spray booths, sewerage treatment plants, hospitals, explosive magazines and more.
Special precautions must be taken for the design, manufacture, installation and use of equipment and cable glands in such hazardous areas. Persons involved in selecting installing and maintaining electrical equipment for use in hazardous areas should be competently trained, have a full understanding of what a hazardous area is and have knowledge of the equipment protection levels and the installation standards involved.
Additional Technical Data on CCG A2EX-VS Double Compression Cable Gland (0436) Part Numbers can be found on the table below. For Conforming Standards & Certificates as well as Fitting Instructions, please advise PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
| Product Code | Gland Size Ref. |
|---|---|
| Product Code043600-16 | Gland Size Ref.00-16ss |
| Product Code043600 | Gland Size Ref.00-20ss |
| Product Code0436-0 | Gland Size Ref.0-20s |
| Product Code043601 | Gland Size Ref.1-20 |
| Product Code043622 | Gland Size Ref.2s-25s |
| Product Code043602 | Gland Size Ref.2-25 |
| Product Code043633 | Gland Size Ref.3s-32s |
| Product Code043603 | Gland Size Ref.3-32 |
| Product Code043644 | Gland Size Ref.4s-40s |
| Product Code043604 | Gland Size Ref.4-40 |
| Product Code043655 | Gland Size Ref.5s-50s |
| Product Code043605 | Gland Size Ref.5-50 |
| Product Code043666 | Gland Size Ref.6s-63s |
| Product Code043606 | Gland Size Ref.6-63 |
| Product Code043677 | Gland Size Ref.7s-75s |
| Product Code043607 | Gland Size Ref.7-75 |
| Product Code043608 | Gland Size Ref.8-80 |
| Product Code043699 | Gland Size Ref.9s-90s |
| Product Code043609 | Gland Size Ref.9-90 |
| Product Code043610 | Gland Size Ref.10-100 |
| Product Code043611 | Gland Size Ref.11-115 |
| Product Code043612 | Gland Size Ref.12-120 |
| Product Code043613 | Gland Size Ref.13-130 |
| All dimensions except NPT are in mm. Intermediate thread sizes are available on request. NPT threads should be tightened “wrench tight”. |