Home>Cable Accessories>Cable Glands & Kits>Hazardous Cable Glands & Kits



CCG Ex Corrosion Guard VS VX VORTEx Barrier Cable Gland (0509) is a Hazardous Area Glanding Device for Unfilled SWA, Aluminium, Copper Tape or Lead Sheathed Cable. Suitable for highly corrosive, wet locations, Group II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
CCG Part Numbers: 050900-16-VX, 050900-VX, 0509-0-VX, 050901-VX, 050922-VX, 050902-VX, 050933-VX, 050903-VX, 050944-VX, 050904-VX, 050955-VX, 050905-VX, 050966-VX, 050906-VX, 050977-VX, 050907-VX, 050908-VX, 050999-VX, 050909-VX, 050910-VX
Features & Benefits
For highly corrosive, wet locations, Group II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
For unfilled hygroscopic multicore cables, refer to IEC 60079-14; 9.3.2 and 10.6.2a, IEC 61892-7, 10.6 and 10.7.
Freely rotating captive cone and inspectable cone ring provides an armour clamp and earth bond on steel wire armour and aluminium armour.
Corrosion Guard® screws onto the gland body and seals over the outer sheath of the cable giving an IP68 and deluge proof seal, protecting the armour and metal parts of the gland.
Provides a 360° earthing to copper tape or lead sheath.
Instantly mixed and injected Resin forms a 100% barrier around the individual cores of the cable.
Prevents explosive gases and/or liquids transmitting down the cable.
Precision manufactured from high-quality brass (Marine Grade Electroless Nickel Plated™).
Supplied with a thread sealing gasket (parallel threads only).
Type: Ex Corrosion Guard VS VX (VORTEx)
Equipment Protection Levels: Ex db IIC, Ex eb IIC, Ex ta IIIC, Ex nR IIC
Gland Material: Brass (Marine Grade Electroless Nickel Plated™)
Seal Material: Standard Thermoset Elastomer or Extreme Temperature Seals, Quick Setting Injection Barrier Resin Seal
Sealing Gasket Material: HDPE, Nylon 66 or PTFE
Cable Type: Steel Wire Armour, Aluminium Armour, Copper Tape or Lead Sheathed
Armour Clamping: Rotating Captive Cone and Inspectable Cone Ring
Sealing Area: Inner Sheath, Outer Sheath and VORTEx Resin around Cable Conductors
Note: The installer should ensure that the materials are suitable for the installation environment.
Installation Standards
IEC/BS EN
IECEx
ATEX
UKEX
INMETRO (Brazil)
TR CU (Russia)
SANS
Ingress Protection
Deluge Protection
Corrosion Protection
Marine ABS
DNV-GL
EMC Compatible
A Hazardous Area is one in which there is potential for an explosion of gases, vapours, mists or dust or a combination of these. Such locations are petrochemical plants, offshore oil rigs, fuel filling stations, timber mills, coal mines, flour mills, paint spray booths, sewerage treatment plants, hospitals, explosive magazines and more.
Special precautions must be taken for the design, manufacture, installation and use of equipment and cable glands in such hazardous areas. Persons involved in selecting installing and maintaining electrical equipment for use in hazardous areas should be competently trained, have a full understanding of what a hazardous area is and have knowledge of the equipment protection levels and the installation standards involved.
Additional Technical Data on CCG Ex Corrosion Guard VS VX VORTEx Barrier Cable Gland (0509) Part Numbers can be found on the table below. For Conforming Standards & Certificates as well as Fitting Instructions, please advise PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
| Product Code | Gland Size Ref. |
|---|---|
| Product Code050900-16-VX | Gland Size Ref.00-16ss |
| Product Code050900-VX | Gland Size Ref.00-20ss |
| Product Code0509-0-VX | Gland Size Ref.0-20s |
| Product Code050901-VX | Gland Size Ref.1-20 |
| Product Code050922-VX | Gland Size Ref.2s-25s |
| Product Code050902-VX | Gland Size Ref.2-25 |
| Product Code050933-VX | Gland Size Ref.3s-32s |
| Product Code050903-VX | Gland Size Ref.3-32 |
| Product Code050944-VX | Gland Size Ref.4s-40s |
| Product Code050904-VX | Gland Size Ref.4-40 |
| Product Code050955-VX | Gland Size Ref.5s-50s |
| Product Code050905-VX | Gland Size Ref.5-50 |
| Product Code050966-VX | Gland Size Ref.6s-63s |
| Product Code050906-VX | Gland Size Ref.6-63 |
| Product Code050977-VX | Gland Size Ref.7s-75s |
| Product Code050907-VX | Gland Size Ref.7-75 |
| Product Code050908-VX | Gland Size Ref.8-80 |
| Product Code050999-VX | Gland Size Ref.9s-90s |
| Product Code050909-VX | Gland Size Ref.9-90 |
| Product Code050910-VX | Gland Size Ref.10-100 |
| All dimensions except NPT are in mm. Intermediate thread sizes are available on request. NPT threads should be tightened ‘wrench tight’. |