Home>Cable Accessories>Cable Glands & Kits>Hazardous Cable Glands & Kits



CCG E1EX-U-VS VX VORTEx Barrier Cable Gland (0586) is a Hazardous Area Glanding Device for Unfilled Multi Armoured Copper Tape or Lead Sheathed Cable. Suitable for indoors, outdoors, Group I, II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
CCG Part Numbers: 058600-16-VX, 058600S-VX, 058600-VX, 0586-0S-VX, 0586-0-VX, 058601-VX, 058622-VX, 058602-VX, 058633-VX, 058603-VX, 058644-VX, 058604-VX, 058655-VX, 058605-VX, 058666-VX, 058606-VX, 058677-VX, 058607-VX, 058608-VX, 058699-VX, 058609-VX, 058610-VX
Features & Benefits
For indoors, outdoors, Group I, II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
For unfilled hygroscopic multicore cables, refer to IEC 60079-14; 9.3.2 and 10.6.2a, IEC 61892-7, 10.6 and 10.7.
Freely rotating captive cone and inspectable cone ring provides an armour clamp and earth bond for steel wire armour and aluminium armour.
Provides 360° earthing to copper tape or lead sheath.
Instantly mixed and injected Resin forms a 100% barrier seal around the individual cores of the cable.
Prevents explosive gases and/or liquids transmitting down the cable.
Precision manufactured from high-quality brass (Marine Grade Electroless Nickel Plated™) available in stainless steel 316/316L on request.
Supplied with a thread sealing gasket (parallel threads only).
Type: E1EX-U-VS VX (VORTEx)
Equipment Protection Levels: Ex db I/IIC, Ex eb I/IIC, Ex ta IIIC, Ex nR IIC
Gland Material: Brass (Marine Grade Electroless Nickel Plated™), Stainless Steel 316/316L
Seal Material: Standard Thermoset Elastomer or Extreme Temperature Seals, Quick Setting Injection Resin Barrier Seal
Sealing Gasket Material: HDPE, Nylon 66 or PTFE
Cable Type: Steel Wire, Aluminium, Braided, Tape Armour and Copper Tape or Lead Sheathed
Armour Clamping: Rotating Captive Cone and Inspectable Cone Ring
Sealing Area: Outer Sheath and VORTEx Resin around Cable Conductors
Optional Accessories: Adaptor, Reducer, Earth Tag, Locknut, Serrated Washer and Shroud
Note: The installer should ensure that the materials are suitable for the installation environment.
Installation Standards
IEC/BS EN
IECEx
ATEX
UKEX
INMETRO (Brazil)
TR CU (Russia)
CCC/CNEx (China)
Ingress Protection
Deluge Protection
Corrosion Protection
Marine ABS
EMC Compatible
A Hazardous Area is one in which there is potential for an explosion of gases, vapours, mists or dust or a combination of these. Such locations are petrochemical plants, offshore oil rigs, fuel filling stations, timber mills, coal mines, flour mills, paint spray booths, sewerage treatment plants, hospitals, explosive magazines and more.
Special precautions must be taken for the design, manufacture, installation and use of equipment and cable glands in such hazardous areas. Persons involved in selecting installing and maintaining electrical equipment for use in hazardous areas should be competently trained, have a full understanding of what a hazardous area is and have knowledge of the equipment protection levels and the installation standards involved.
Additional Technical Data on CCG E1EX-U-VS VX VORTEx Barrier Cable Gland (0586) Part Numbers can be found on the table below. For Conforming Standards & Certificates as well as Fitting Instructions, please advise PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
| Product Code | Gland Size Ref. |
|---|---|
| Product Code058600-16-VX | Gland Size Ref.00-16ss |
| Product Code058600S-VX | Gland Size Ref.00s-20ss |
| Product Code058600-VX | Gland Size Ref.00-20ss |
| Product Code0586-0S-VX | Gland Size Ref.0s-20s |
| Product Code0586-0-VX | Gland Size Ref.0-20s |
| Product Code058601-VX | Gland Size Ref.1-20 |
| Product Code058622-VX | Gland Size Ref.2s-25s |
| Product Code058602-VX | Gland Size Ref.2-25 |
| Product Code058633-VX | Gland Size Ref.3s-32s |
| Product Code058603-VX | Gland Size Ref.3-32 |
| Product Code058644-VX | Gland Size Ref.4s-40s |
| Product Code058604-VX | Gland Size Ref.4-40 |
| Product Code058655-VX | Gland Size Ref.5s-50s |
| Product Code058605-VX | Gland Size Ref.5-50 |
| Product Code058666-VX | Gland Size Ref.6s-63s |
| Product Code058606-VX | Gland Size Ref.6-63 |
| Product Code058677-VX | Gland Size Ref.7s-75s |
| Product Code058607-VX | Gland Size Ref.7-75 |
| Product Code058608-VX | Gland Size Ref.8-80 |
| Product Code058699-VX | Gland Size Ref.9s-90s |
| Product Code058609-VX | Gland Size Ref.9-90 |
| Product Code058610-VX | Gland Size Ref.10-100 |
| All dimensions except NPT are in mm. Intermediate thread sizes are available on request. NPT threads should be tightened ‘wrench tight’. |