Home>Cable Accessories>Cable Glands & Kits>Industrial Cable Glands & Kits



CCG CXe Deluge Seal Cable Gland (0570) is a Hazardous Area Glanding Device for Braided and Steel Tape Cable. Suitable for indoor, outdoor, Group II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
CCG Part Numbers: 057000-16, 057000, 0570-0-16, 0570-0, 057001, 057022, 057002, 057033, 057003, 057044, 057004, 057055, 057005, 057066, 057006, 057077, 057007, 057008, 057099, 057009, 057010
Features & Benefits
For indoor, outdoor, Group II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
Two-piece handling, no loose parts.
Freely rotating captive cone and inspectable cone ring, providing an armour clamp and earth bond without twisting the armouring.
With a patented Variable Deluge Seal™ as standard.
Provides a seal on the outer sheath of the cable sealing to IP68.
Patented disconnect armoured clamp system for ease of inspection.
Precision manufactured from high-quality brass (Marine Grade Electroless Nickel Plated™) available in stainless steel 316/316L on request.
Supplied with a thread sealing gasket (parallel threads only).
Type: CXe
Equipment Protection Levels: Ex eb IIC, Ex ta IIIC
Gland Material: Brass (Marine Grade Electroless Nickel Plated™), Stainless Steel 316/316L
Seal Material: Thermoset Elastomer
Sealing Gasket Material: HDPE, Nylon 66 or PTFE
Cable Type: Braid, Steel Tape Armour
Armour Clamping: Rotating Captive Cone and Inspectable Cone Ring
Sealing Area: Outer Sheath and Variable Deluge Seal™
Optional Accessories: Adaptor, Reducer, Earth Tag, Locknut, Serrated Washer and Shroud
Note: The installer should ensure that the materials are suitable for the installation environment.
Installation Standards
IEC/BS EN
IECEx
ATEX
UKEX
INMETRO (Brazil)
TR CU (Russia)
SANS
Ingress Protection
Deluge Protection
Corrosion Protection
Marine ABS
DNV-GL
EMC Compatible
A Hazardous Area is one in which there is potential for an explosion of gases, vapours, mists or dust or a combination of these. Such locations are petrochemical plants, offshore oil rigs, fuel filling stations, timber mills, coal mines, flour mills, paint spray booths, sewerage treatment plants, hospitals, explosive magazines and more.
Special precautions must be taken for the design, manufacture, installation and use of equipment and cable glands in such hazardous areas. Persons involved in selecting installing and maintaining electrical equipment for use in hazardous areas should be competently trained, have a full understanding of what a hazardous area is and have knowledge of the equipment protection levels and the installation standards involved.
Additional Technical Data on CCG CXe Deluge Seal Cable Gland (0570) Part Numbers can be found on the table below. For Conforming Standards & Certificates as well as Fitting Instructions, please advise PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
| Product Code | Gland Size Ref. |
|---|---|
| Product Code057000-16 | Gland Size Ref.00-16ss |
| Product Code057000 | Gland Size Ref.00-20ss |
| Product Code0570-0-16 | Gland Size Ref.0-16s |
| Product Code0570-0 | Gland Size Ref.0-20s |
| Product Code057001 | Gland Size Ref.1-20 |
| Product Code057022 | Gland Size Ref.2s-25s |
| Product Code057002 | Gland Size Ref.2-25 |
| Product Code057033 | Gland Size Ref.3s-32 |
| Product Code057003 | Gland Size Ref.3-32 |
| Product Code057044 | Gland Size Ref.4s-40s |
| Product Code057004 | Gland Size Ref.4-40 |
| Product Code057055 | Gland Size Ref.5s-50s |
| Product Code057005 | Gland Size Ref.5-50 |
| Product Code057066 | Gland Size Ref.6s-63s |
| Product Code057006 | Gland Size Ref.6-63 |
| Product Code057077 | Gland Size Ref.7s-75s |
| Product Code057007 | Gland Size Ref.7-75 |
| Product Code057008 | Gland Size Ref.8-80 |
| Product Code057099 | Gland Size Ref.9s-90s |
| Product Code057009 | Gland Size Ref.9-90 |
| Product Code057010 | Gland Size Ref.10-100 |
| All dimensions except NPT are in mm. Intermediate thread sizes are available on request. NPT threads should be tightened ‘wrench tight’. |