Home>Cable Accessories>Separable Connectors>Nexans Euromold Separable Connectors






Nexans Euromold 151SP Straight Plug is a separable straight plug designed to connect polymeric insulated cable to cable. Mates with the elbow, straight and branch joint connectors.
Part Numbers: 151SP, K151SP.
Euromold 151SP is a separable straight plug specified to terminate and connect medium/high voltage cables in the following voltage classes:
6/10 (12kV)
6.35/11 (12kV)
8.7/15 (17.5kV)
12/20 (24kV)
12.7/22 (24kV)
Technical Characteristics
The thick conductive EPDM jacket provides a total safe to touch screen, ensuring personnel safety.
Each straight plug is tested for AC withstand and partial discharge prior to leaving the factory.
Specification & Design
Euromold
Type 151SP Voltage
Um Current
Ir Conductor Size
Min-Max
151SP 12 kV 200 Amps 16-95 mm2
Conductive EPDM insert.
Conductive EPDM jacket.
Insulating EPDM layer moulded between the insert and the jacket.
Type A interface as described by CENELEC EN 50180 and 50181.
Conductor contact.
The complete (K)151SP straight plug kit comprises the following components. The kit also comprises silicon grease, wipers, installation instructions and crimp chart.
For Ordering Instructions and Part Number Selection Table of Nexans Euromold 151SP Straight Plugs (K151SP), please refer to the Technical Data Table Below. For additional General and Technical Information, download the PDF files.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
| Euromold Type 151SP | Voltage Um |
|---|---|
| Euromold Type 151SP151SP | Voltage Um12 kV |
| Euromold Type 151SPK151SP | Voltage Um24 kV |
| ORDERING INSTRUCTIONS FOR 151SP To order the straight plug, select the part number which gives the best centring to the cable core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV. Example: The copper wire screened cable is 12 kV, 50 mm2 stranded aluminium with a diameter over core insulation of 16,9 mm. Order a 151SP-A-50(K)M-12-2+11TL-FA/FAB straight plug kit. | |
| PART NUMBER | DIAMETER OVER CORE INSULATION MIN |
| PART NUMBER151SP-A-X+11TL-FA/FAB | DIAMETER OVER CORE INSULATION MIN14.6 mm |
| PART NUMBER151SP-B-X+11TL-FB/FG | DIAMETER OVER CORE INSULATION MIN17.2 mm |
| PART NUMBER151SP-B-X+11TL-GA/GAB | DIAMETER OVER CORE INSULATION MIN19.7 mm |
| PART NUMBER151SP-C-X+11TL-GB/GH | DIAMETER OVER CORE INSULATION MIN22.2 mm |
| TABLE X - ALUMINIUM & COPPER CONDUCTOR | |
| CONDUCTOR SIZE | Alu Conductor DIN Hexagonal |
| CONDUCTOR SIZE16 mm2 | Alu Conductor DIN Hexagonal- |
| CONDUCTOR SIZE25 mm2 | Alu Conductor DIN Hexagonal25(K)M-12-2 |
| CONDUCTOR SIZE35 mm2 | Alu Conductor DIN Hexagonal35(K)M-12-2 |
| CONDUCTOR SIZE50 mm2 | Alu Conductor DIN Hexagonal50(K)M-12-2 |
| CONDUCTOR SIZE70 mm2 | Alu Conductor DIN Hexagonal70(K)M-12-2 |
| CONDUCTOR SIZE95 mm2 | Alu Conductor DIN Hexagonal95(K)M-12-2 |