Home>Cable Accessories>Separable Connectors>Nexans Euromold Separable Connectors






Nexans Euromold 804PB Separable Coupling Connector is a coupling connector (bolted type) for dual arrangement. Designed to be used with 480TB, 484TB and 489TB Separable Tee Connectors and meets the requirements of CENELEC HD 629,1. Can also be installed on any 8-series coupling connector for a multiple cable arrangement.
Type 804PB Part Numbers: 804PB/G, K804PB/G, M804PB/G, P804PB/G.
Euromold 804PB is a bolted separable coupling connector specified to terminate and connect medium/high voltage cables in the following voltage classes:
6/10 (12kV)
6.35/11 (12kV)
8.7/15 (17.5kV)
12/20 (24kV)
12.7/22 (24kV)
18/30 (36kV)
19/33 (36kV)
20.8/36 (42kV)
Technical Characteristics
A thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel.
Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
The 804PB separable connector meets the requirements of CENELEC HD 629,1.
Euromold
Type 804PB Voltage
Um Current
Ir Conductor Size
Min-Max
804PB/G 12 kV 1250 Amps 240-630 mm2
K804PB/G 24 kV 1250 Amps 240-630 mm2
M804PB/G 36 kV 1250 Amps 240-630 mm2
Interface designed to fit 480TB, 484TB and 489TB connectors
Contact rod for 804PB
Conductor contact
Conductive EPDM insert
Conductive EPDM jacket
Insulating EPDM layer moulded between the insert and the jacket
Cable reducer
Conductive EPDM cap
Basic insulating plug (with VD point)
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
The complete (K)(M)(P)804PB/G coupling connector kit comprises 3 x the following components. The kit also comprises silicone grease, field control mastic, gloves, wipers, roll adhesive tape, installation instructions and crimp chart.
For Ordering Instructions and Part Number Selection Table of Nexans Euromold 804PB Separable Coupling Connector (804PB/G, K804PB/G, M804PB/G, P804PB/G), please refer to the Technical Data Table Below. For additional General and Technical Information, download the PDF files.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
| Euromold Type 804PB | Voltage Um |
|---|---|
| Euromold Type 804PB804PB/G | Voltage Um12 kV |
| Euromold Type 804PBK804PB/G | Voltage Um24 kV |
| Euromold Type 804PBM804PB/G | Voltage Um36 kV |
| Euromold Type 804PBP804PB/G | Voltage Um42 kV |
| ORDERING INSTRUCTIONS FOR (K)(M)(P)804PB To order the coupling connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV and a 'P' for use up to 42 kV. Example: The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37 mm. Order 3 x M804PB/G-S-32-240BI2 coupling connector kit. | |
| PART NUMBER | DIAMETER OVER CORE INSULATION MIN |
| PART NUMBER3 x 804PB/G-S-22-X | DIAMETER OVER CORE INSULATION MIN23.5 mm |
| PART NUMBER3 x 804PB/G-S-27-X | DIAMETER OVER CORE INSULATION MIN28.5 mm |
| PART NUMBER3 x 804PB/G-S-32-X | DIAMETER OVER CORE INSULATION MIN34 mm |
| PART NUMBER3 x 804PB/G-S-37-X | DIAMETER OVER CORE INSULATION MIN39 mm |
| PART NUMBER3 x 804PB/G-S-43-X | DIAMETER OVER CORE INSULATION MIN45.5 mm |
| TABLE X - CONNECTORS SUITABLE FOR COPPER & ALUMINIUM CABLES | |
| CONDUCTOR SIZE | Alu Conductor DIN Hexagonal |
| CONDUCTOR SIZE240 mm2 | Alu Conductor DIN Hexagonal240BI2 |
| CONDUCTOR SIZE300 mm2 | Alu Conductor DIN Hexagonal300BI2 |
| CONDUCTOR SIZE400 mm2 | Alu Conductor DIN Hexagonal400BI2 |
| CONDUCTOR SIZE500 mm2 | Alu Conductor DIN Hexagonal500BI2 |
| CONDUCTOR SIZE630 mm2 | Alu Conductor DIN Hexagonal- |